Flush Water Testing in Dubai, UAE

Enquiry:

We are currently carrying out the chemical cleaning and flushing of a chilled water piping system associated with a Carrier Chiller installation and require third-party laboratory testing of the flushing water sample to verify satisfactory completion of the chemical cleaning process.

The cleaning process was performed using the following chemicals:

• TIG Group 104L – Acidic Cleaning Chemical
• TIG Group 112L – Alkaline Cleaning / Neutralizing Chemical

In this regard, kindly provide your quotation for laboratory testing and analysis of the submitted water sample covering the following parameters:

ParameterAcceptance Criteria
AppearanceClear, Colorless, Odorless
pH7.0 – 8.5
Conductivity< 450 µS/cm
Suspended Solids (TSS)< 5 mg/L
Turbidity< 10 NTU
Total Iron (Fe)< 0.5 mg/L (ppm)
Total Hardness50 – 100 ppm
Chloride (Cl-)Report Value
Sulphate (SO₄²⁻)Report Value
Total Dissolved Solids (TDS)Report Value
Residual Acidity / AlkalinityReport Value
Copper (Cu)Report Value
Biological Activity / Bacteria Count (if available)Report Value

Additionally, we request that the test report include a clear statement indicating that:

  • The sample meets the requirements for satisfactory completion of chemical cleaning and flushing.
  • The system has been adequately neutralized following acidic and alkaline cleaning.

Kindly provide your quotation, sample volume requirements, turnaround time for testing, and any specific sample collection or preservation requirements.


One of our highly proficient and ISO certified laboratory would be taking over this job.

Should you have any similar requisites, do drop us email and we shall revert instantly -> [email protected].