Pipeline of different fluids/liquids like chillers and chilled water always require periodic cleaning with chemical and through flushing. We aim to provide appropriate testing methods and parameters that comply with local and international standards i.e ISO etc.
Here is main and standard group of parameters for flushing water testing:
| Parameter | Acceptance Criteria |
| Appearance | Clear, Colorless, Odorless |
| pH | 7.0 – 8.5 |
| Conductivity | < 450 µS/cm |
| Suspended Solids (TSS) | < 5 mg/L |
| Turbidity | < 10 NTU |
| Total Iron (Fe) | < 0.5 mg/L (ppm) |
| Total Hardness | 50 – 100 ppm |
| Chloride (Cl-) | Report Value |
| Sulphate (SO₄²⁻) | Report Value |
| Total Dissolved Solids (TDS) | Report Value |
| Residual Acidity / Alkalinity | Report Value |
| Copper (Cu) | Report Value |
| Biological Activity / Bacteria Count (if available) | Report Value |